Triangulation and 3D location estimation of RFI and partial discharge sources within a 400kV substation

Brian G. Stewart, Alan Nesbitt, L. Hall

    Research output: Chapter in Book/Report/Conference proceedingConference contribution

    Abstract

    The 3D location of RFI (Radio Frequency Interference) and PD (Partial Discharge) sources within a 400 kV substation are presented in this paper. The technique involves the employment of four small broadband mobile antennas attached to a fast digitizing scope. The time differences of arrival within a group of four received digitized signals are used to triangulate the 3D position of radiating RF sources. Results presented demonstrate the capability of the technique. Two specific locations at heights of around 7 m and 9 m pinpointed regions associated with the surrounding joint areas of a recently refurbished bus bar. Deformed inner cable cores were discovered at one of these locations. After remedial attention, cleaning and reconnection of the bus bar the RFI problems disappeared. Other RFI source locations were pinpointed, and surprisingly, some of these were related to nearby lighting.

    Original languageEnglish
    Title of host publicationProceedings of the IEEE Electrical Insulation Conference 2009
    PublisherIEEE
    ISBN (Print)9781424439157
    DOIs
    Publication statusPublished - 1 Jan 2009

    Keywords

    • radio frequency interference
    • RFI
    • PD
    • electrical engineering

    Fingerprint Dive into the research topics of 'Triangulation and 3D location estimation of RFI and partial discharge sources within a 400kV substation'. Together they form a unique fingerprint.

  • Cite this

    Stewart, B. G., Nesbitt, A., & Hall, L. (2009). Triangulation and 3D location estimation of RFI and partial discharge sources within a 400kV substation. In Proceedings of the IEEE Electrical Insulation Conference 2009 IEEE. https://doi.org/10.1109/EIC.2009.5166337