Enhanced condition monitoring of power transformers through improvement in accuracy of DGA interpretation

Ehnaish Aburaghiega, Mohamed Emad Farrag, Donald Hepburn, Belen Garcia

Research output: Chapter in Book/Report/Conference proceedingConference contribution

39 Downloads (Pure)

Abstract

Transformer failure in electricity supply grids has a high financial impact, due to failure to meet commercial contract and possibility of transformer replacement cost. Therefore, detecting fault inception is very important in order to keep the transformer operating with recommended efficiency, hence ensuring stability of the electric network. Dissolved gas analysis (DGA) of a transformer can provide clear indication of thermal and electrical stresses on power transformer insulation and is considered as one of the most effective tools for oil-filled power transformer diagnostics. DGA is used to detect incipient faults in order to manage the fault severity. Both on-line and off-line condition monitoring methods can be applied to obtain gas content, thereafter there are many interpretation techniques for DGA results. The accuracy of these techniques is dependent on the operator’s experience and knowledge of the materials and equipment involved. In this work, a combined fuzzy logic analysis technique for monitoring of power transformers based on DGA analysis is proposed, the system uses the 7 key gases to diagnose the health of the transformer and, where applicable, fault type. Initially, gas levels are considered using the IEEE standard as a basis to indicate the health of the transformer. A combined fuzzified analytical tool, based on Duval Triangle, Doernenburg ratio and Key gas method, are analysed to identify the fault type, improving on the accuracy of the individual interpretation techniques. The analytical tool has been applied to 444 sample faults reported in the literature to assess the accuracy of the proposed system. Results presented show the system’s overall decision has improved capability of identifying the transformer condition over individual methods. The proposed system is proved to have 99 % accuracy in identifying the transformer normality. For cases where transformers were faulty, the approach has 98.76% accuracy in recognising the actual fault, superior to individual approaches.
Original languageEnglish
Title of host publication51st International Universities Power Engineering Conference (UPEC)
PublisherIEEE
Pages1-6
Number of pages6
ISBN (Electronic)9781509046508
DOIs
Publication statusPublished - 20 Nov 2017

Fingerprint

Gas fuel analysis
Power transformers
Condition monitoring
Gases
Health
Circuit theory
Fuzzy logic
Insulation
Electricity
Monitoring
Costs

Keywords

  • power transformer monitoring, DGA, duval triangle, Doernenburg ratio, key gas

Cite this

Aburaghiega, E., Farrag, M. E., Hepburn, D., & Garcia, B. (2017). Enhanced condition monitoring of power transformers through improvement in accuracy of DGA interpretation. In 51st International Universities Power Engineering Conference (UPEC) (pp. 1-6). IEEE. https://doi.org/10.1109/UPEC.2016.8114060
Aburaghiega, Ehnaish ; Farrag, Mohamed Emad ; Hepburn, Donald ; Garcia, Belen. / Enhanced condition monitoring of power transformers through improvement in accuracy of DGA interpretation. 51st International Universities Power Engineering Conference (UPEC). IEEE, 2017. pp. 1-6
@inproceedings{9ddee2f19cbb4f44a2bcadee51f816cb,
title = "Enhanced condition monitoring of power transformers through improvement in accuracy of DGA interpretation",
abstract = "Transformer failure in electricity supply grids has a high financial impact, due to failure to meet commercial contract and possibility of transformer replacement cost. Therefore, detecting fault inception is very important in order to keep the transformer operating with recommended efficiency, hence ensuring stability of the electric network. Dissolved gas analysis (DGA) of a transformer can provide clear indication of thermal and electrical stresses on power transformer insulation and is considered as one of the most effective tools for oil-filled power transformer diagnostics. DGA is used to detect incipient faults in order to manage the fault severity. Both on-line and off-line condition monitoring methods can be applied to obtain gas content, thereafter there are many interpretation techniques for DGA results. The accuracy of these techniques is dependent on the operator’s experience and knowledge of the materials and equipment involved. In this work, a combined fuzzy logic analysis technique for monitoring of power transformers based on DGA analysis is proposed, the system uses the 7 key gases to diagnose the health of the transformer and, where applicable, fault type. Initially, gas levels are considered using the IEEE standard as a basis to indicate the health of the transformer. A combined fuzzified analytical tool, based on Duval Triangle, Doernenburg ratio and Key gas method, are analysed to identify the fault type, improving on the accuracy of the individual interpretation techniques. The analytical tool has been applied to 444 sample faults reported in the literature to assess the accuracy of the proposed system. Results presented show the system’s overall decision has improved capability of identifying the transformer condition over individual methods. The proposed system is proved to have 99 {\%} accuracy in identifying the transformer normality. For cases where transformers were faulty, the approach has 98.76{\%} accuracy in recognising the actual fault, superior to individual approaches.",
keywords = "power transformer monitoring, DGA, duval triangle, Doernenburg ratio, key gas",
author = "Ehnaish Aburaghiega and Farrag, {Mohamed Emad} and Donald Hepburn and Belen Garcia",
note = "Acceptance in SAN Removed Year 1-2 exception as no longer needed after Pure migration. ET 25/9/19",
year = "2017",
month = "11",
day = "20",
doi = "10.1109/UPEC.2016.8114060",
language = "English",
pages = "1--6",
booktitle = "51st International Universities Power Engineering Conference (UPEC)",
publisher = "IEEE",

}

Aburaghiega, E, Farrag, ME, Hepburn, D & Garcia, B 2017, Enhanced condition monitoring of power transformers through improvement in accuracy of DGA interpretation. in 51st International Universities Power Engineering Conference (UPEC). IEEE, pp. 1-6. https://doi.org/10.1109/UPEC.2016.8114060

Enhanced condition monitoring of power transformers through improvement in accuracy of DGA interpretation. / Aburaghiega, Ehnaish; Farrag, Mohamed Emad; Hepburn, Donald; Garcia, Belen.

51st International Universities Power Engineering Conference (UPEC). IEEE, 2017. p. 1-6.

Research output: Chapter in Book/Report/Conference proceedingConference contribution

TY - GEN

T1 - Enhanced condition monitoring of power transformers through improvement in accuracy of DGA interpretation

AU - Aburaghiega, Ehnaish

AU - Farrag, Mohamed Emad

AU - Hepburn, Donald

AU - Garcia, Belen

N1 - Acceptance in SAN Removed Year 1-2 exception as no longer needed after Pure migration. ET 25/9/19

PY - 2017/11/20

Y1 - 2017/11/20

N2 - Transformer failure in electricity supply grids has a high financial impact, due to failure to meet commercial contract and possibility of transformer replacement cost. Therefore, detecting fault inception is very important in order to keep the transformer operating with recommended efficiency, hence ensuring stability of the electric network. Dissolved gas analysis (DGA) of a transformer can provide clear indication of thermal and electrical stresses on power transformer insulation and is considered as one of the most effective tools for oil-filled power transformer diagnostics. DGA is used to detect incipient faults in order to manage the fault severity. Both on-line and off-line condition monitoring methods can be applied to obtain gas content, thereafter there are many interpretation techniques for DGA results. The accuracy of these techniques is dependent on the operator’s experience and knowledge of the materials and equipment involved. In this work, a combined fuzzy logic analysis technique for monitoring of power transformers based on DGA analysis is proposed, the system uses the 7 key gases to diagnose the health of the transformer and, where applicable, fault type. Initially, gas levels are considered using the IEEE standard as a basis to indicate the health of the transformer. A combined fuzzified analytical tool, based on Duval Triangle, Doernenburg ratio and Key gas method, are analysed to identify the fault type, improving on the accuracy of the individual interpretation techniques. The analytical tool has been applied to 444 sample faults reported in the literature to assess the accuracy of the proposed system. Results presented show the system’s overall decision has improved capability of identifying the transformer condition over individual methods. The proposed system is proved to have 99 % accuracy in identifying the transformer normality. For cases where transformers were faulty, the approach has 98.76% accuracy in recognising the actual fault, superior to individual approaches.

AB - Transformer failure in electricity supply grids has a high financial impact, due to failure to meet commercial contract and possibility of transformer replacement cost. Therefore, detecting fault inception is very important in order to keep the transformer operating with recommended efficiency, hence ensuring stability of the electric network. Dissolved gas analysis (DGA) of a transformer can provide clear indication of thermal and electrical stresses on power transformer insulation and is considered as one of the most effective tools for oil-filled power transformer diagnostics. DGA is used to detect incipient faults in order to manage the fault severity. Both on-line and off-line condition monitoring methods can be applied to obtain gas content, thereafter there are many interpretation techniques for DGA results. The accuracy of these techniques is dependent on the operator’s experience and knowledge of the materials and equipment involved. In this work, a combined fuzzy logic analysis technique for monitoring of power transformers based on DGA analysis is proposed, the system uses the 7 key gases to diagnose the health of the transformer and, where applicable, fault type. Initially, gas levels are considered using the IEEE standard as a basis to indicate the health of the transformer. A combined fuzzified analytical tool, based on Duval Triangle, Doernenburg ratio and Key gas method, are analysed to identify the fault type, improving on the accuracy of the individual interpretation techniques. The analytical tool has been applied to 444 sample faults reported in the literature to assess the accuracy of the proposed system. Results presented show the system’s overall decision has improved capability of identifying the transformer condition over individual methods. The proposed system is proved to have 99 % accuracy in identifying the transformer normality. For cases where transformers were faulty, the approach has 98.76% accuracy in recognising the actual fault, superior to individual approaches.

KW - power transformer monitoring, DGA, duval triangle, Doernenburg ratio, key gas

U2 - 10.1109/UPEC.2016.8114060

DO - 10.1109/UPEC.2016.8114060

M3 - Conference contribution

SP - 1

EP - 6

BT - 51st International Universities Power Engineering Conference (UPEC)

PB - IEEE

ER -

Aburaghiega E, Farrag ME, Hepburn D, Garcia B. Enhanced condition monitoring of power transformers through improvement in accuracy of DGA interpretation. In 51st International Universities Power Engineering Conference (UPEC). IEEE. 2017. p. 1-6 https://doi.org/10.1109/UPEC.2016.8114060